Switchgear insulating gas: moisture in SF₆ and SF₆-free mixtures
Follow the gas from the cylinder through the handling cart into the switchgear and back to recovery. Tap each point to see what is measured and which YORK hygrometer fits.
Regulation (EU) 2024/573 phases out new F-gas switchgear in steps from 2026, so utilities across Europe are moving to CO₂-based mixtures and technical air. The new gases still have to be dry, and the dew point is checked at filling, at commissioning and during maintenance, just as with SF₆.
Tap a numbered point. Swipe the diagram sideways on a phone.
How the process works
- Gas supply. New SF₆ or alternative mixtures arrive in cylinders with the supplier's specification.
- Filling. A gas handling cart evacuates the compartment and fills it to rated pressure.
- Commissioning. Moisture is checked before the switchgear is energised.
- Maintenance. Moisture is checked at intervals set by the utility and after any opening of the compartment.
- Recovery. Gas is recovered into cylinders, processed and reused or sent for reclamation.
Values are typical figures from published specifications and industry practice. Your plant, licensor or grid specification always governs.
Measurement points at a glance
| # | Point | Measures | Typical value / limit | YORK instrument |
|---|---|---|---|---|
| 1 | New gas before filling | Moisture in SF₆ or the alternative mixture | Gas supplier's specification; for example, draft IEC 63360 gives ≤ 70 ppmv water for technical-grade C4-FN | DM9600P, DM9600PL |
| 2 | Compartment after filling (commissioning) | Frost point at filling pressure | One C4-FN mixture handbook gives ≤ −10 °C with adsorber and ≤ −15 °C without; the equipment maker's values govern | DM9600PL, DM9600P |
| 3 | Compartment in service (maintenance) | Frost point at filling pressure | The same handbook gives ≤ −5 °C during service life; utilities set their own intervals | DM9600PL |
| 4 | Recovered gas before reuse | Moisture after processing on the cart | SF₆ reuse criteria are given in IEC 60480; mixtures follow the manufacturer | DM9600PL |
| 5 | Gas laboratory | Reference dew point on sample bottles | Laboratory reference to −70 °C frost point | DM9700 |
Questions we are asked
Can a chilled mirror measure CO₂-based switchgear mixtures?
Yes. It measures dew point directly, so it suits C4-FN/CO₂ mixtures and technical air as well as SF₆.
Which YORK hygrometer suits field work?
The portable DM9600PL reaches −70 °C frost point and the DM9600P −60 °C; the DM9700 is the laboratory reference.
Should the sample gas be vented?
No. Fluorinated mixtures still have a global warming potential. Return the sample to a recovery cylinder.