Switchgear insulating gas: moisture in SF₆ and SF₆-free mixtures

Follow the gas from the cylinder through the handling cart into the switchgear and back to recovery. Tap each point to see what is measured and which YORK hygrometer fits.

Regulation (EU) 2024/573 phases out new F-gas switchgear in steps from 2026, so utilities across Europe are moving to CO₂-based mixtures and technical air. The new gases still have to be dry, and the dew point is checked at filling, at commissioning and during maintenance, just as with SF₆.

SAMPLE BOTTLENEW GASCYLINDERSGAS HANDLING CART(FILL / RECOVER)GAS-INSULATED SUBSTATIONBAY 1BAY 2BAY 3RECOVERYCYLINDERGAS LABORATORY1H₂O2FP3FP4H₂O5H₂O
YORK instrumentIntegrated system (supplied through YORK)

Tap a numbered point. Swipe the diagram sideways on a phone.

Request a quote for this point →
Auto tour
Project list 0 →

How the process works

  1. Gas supply. New SF₆ or alternative mixtures arrive in cylinders with the supplier's specification.
  2. Filling. A gas handling cart evacuates the compartment and fills it to rated pressure.
  3. Commissioning. Moisture is checked before the switchgear is energised.
  4. Maintenance. Moisture is checked at intervals set by the utility and after any opening of the compartment.
  5. Recovery. Gas is recovered into cylinders, processed and reused or sent for reclamation.
About the values

Values are typical figures from published specifications and industry practice. Your plant, licensor or grid specification always governs.

Measurement points at a glance

#PointMeasuresTypical value / limitYORK instrument
1New gas before fillingMoisture in SF₆ or the alternative mixtureGas supplier's specification; for example, draft IEC 63360 gives ≤ 70 ppmv water for technical-grade C4-FNDM9600P, DM9600PL
2Compartment after filling (commissioning)Frost point at filling pressureOne C4-FN mixture handbook gives ≤ −10 °C with adsorber and ≤ −15 °C without; the equipment maker's values governDM9600PL, DM9600P
3Compartment in service (maintenance)Frost point at filling pressureThe same handbook gives ≤ −5 °C during service life; utilities set their own intervalsDM9600PL
4Recovered gas before reuseMoisture after processing on the cartSF₆ reuse criteria are given in IEC 60480; mixtures follow the manufacturerDM9600PL
5Gas laboratoryReference dew point on sample bottlesLaboratory reference to −70 °C frost pointDM9700

Questions we are asked

Can a chilled mirror measure CO₂-based switchgear mixtures?

Yes. It measures dew point directly, so it suits C4-FN/CO₂ mixtures and technical air as well as SF₆.

Which YORK hygrometer suits field work?

The portable DM9600PL reaches −70 °C frost point and the DM9600P −60 °C; the DM9700 is the laboratory reference.

Should the sample gas be vented?

No. Fluorinated mixtures still have a global warming potential. Return the sample to a recovery cylinder.