Oxygen reduction fire prevention: oxygen in data halls and warehouses

Follow nitrogen from the generator into protected rooms and the sample lines back to the control panel. Tap each point to see what is measured and which YORK analyzer fits.

Oxygen reduction systems, common in data centres, archives and automated warehouses in the UK, the Nordics and Singapore, keep a room's oxygen below the level at which a fire can develop. The system is only as good as its oxygen measurement.

SAMPLEAIR COMPRESSORFILTER /DRYERN₂ GENERATOR(MEMBRANE / PSA)DATA HALL (PROTECTED ROOM)SERVER RACKSARCHIVE / WAREHOUSEO₂ CONTROLPANEL1O₂ %2O₂ %3O₂4PDP5O₂
YORK instrumentIntegrated system (supplied through YORK)

Tap a numbered point. Swipe the diagram sideways on a phone.

Request a quote for this point →
Auto tour
Project list 0 →

How the process works

  1. Compressed air. A compressor and dryer supply clean, dry air to the generator.
  2. Nitrogen generation. A membrane or PSA generator produces nitrogen-enriched air.
  3. Oxygen reduction. Nitrogen is fed into the protected room until oxygen reaches the design level.
  4. Control. Sample lines feed an oxygen control panel that starts and stops the supply.
  5. Access. Entry rules and alarms follow the oxygen level and national regulations.
About the values

Values are typical figures from published specifications and industry practice. Your plant, licensor or grid specification always governs.

Measurement points at a glance

#PointMeasuresTypical value / limitYORK instrument
1Data hall atmosphereOxygen in the roomTypically held around 15% O₂ by volume; the design level depends on the materials protected (EN 16750)PGA530
2Archive or warehouseOxygen in the roomDesign level set per room by the risk assessment (EN 16750)PGA530
3Nitrogen generator outletResidual oxygenGenerators for oxygen reduction commonly deliver about 90–95% N₂PGA530
4Compressed air to the generatorPressure dew pointSet by the generator supplierDPT810
5Room sensor check and staff entryOxygen, portable checkEntry rules depend on the oxygen level and national regulationsPOA300

Questions we are asked

Which analyzer suits room oxygen control?

The PGA530 in-line percent oxygen analyzer covers 0–100% O₂; the portable POA300 checks sensors and conditions before entry.

What oxygen level is used?

Around 15% O₂ is typical for data halls; the design level depends on the materials protected and follows EN 16750.

Do I need a dew point check?

Yes, on the compressed air to the generator. Water and oil shorten the life of membranes and adsorbents.