- Oxygen reduction fire prevention
Industries
Oxygen reduction fire prevention: oxygen in data halls and warehouses
Follow nitrogen from the generator into protected rooms and the sample lines back to the control panel. Tap each point to see what is measured and which YORK analyzer fits.
Oxygen reduction systems, common in data centres, archives and automated warehouses in the UK, the Nordics and Singapore, keep a room's oxygen below the level at which a fire can develop. The system is only as good as its oxygen measurement.
Tap a numbered point. Swipe the diagram sideways on a phone.
How the process works
- Compressed air. A compressor and dryer supply clean, dry air to the generator.
- Nitrogen generation. A membrane or PSA generator produces nitrogen-enriched air.
- Oxygen reduction. Nitrogen is fed into the protected room until oxygen reaches the design level.
- Control. Sample lines feed an oxygen control panel that starts and stops the supply.
- Access. Entry rules and alarms follow the oxygen level and national regulations.
Values are typical figures from published specifications and industry practice. Your plant, licensor or grid specification always governs.
Measurement points at a glance
| # | Point | Measures | Typical value / limit | YORK instrument |
|---|---|---|---|---|
| 1 | Data hall atmosphere | Oxygen in the room | Typically held around 15% O₂ by volume; the design level depends on the materials protected (EN 16750) | PGA530 |
| 2 | Archive or warehouse | Oxygen in the room | Design level set per room by the risk assessment (EN 16750) | PGA530 |
| 3 | Nitrogen generator outlet | Residual oxygen | Generators for oxygen reduction commonly deliver about 90–95% N₂ | PGA530 |
| 4 | Compressed air to the generator | Pressure dew point | Set by the generator supplier | DPT810 |
| 5 | Room sensor check and staff entry | Oxygen, portable check | Entry rules depend on the oxygen level and national regulations | POA300 |
Questions we are asked
Which analyzer suits room oxygen control?
The PGA530 in-line percent oxygen analyzer covers 0–100% O₂; the portable POA300 checks sensors and conditions before entry.
What oxygen level is used?
Around 15% O₂ is typical for data halls; the design level depends on the materials protected and follows EN 16750.
Do I need a dew point check?
Yes, on the compressed air to the generator. Water and oil shorten the life of membranes and adsorbents.